Standard Glossary Of  Electrical  Terms

 

Alternating Current

A flow of electrical current which increases to a maximum in one direction, decreases to zero, and then reverses direction and reaches maximum in the other direction and back so zero. The cycle is repeated continuously. The number of such cycles per second is equal to the frequency and is measured in “Hertz”. U.S. commercial power is 60 Hertz (i.e. 60 cycles per second).
 

Aerial

Above ground installation for power lines or telephone lines or cables are installed on a pole or overhead structure.

 

Ammeter

Electrical test instrument used to measure current in a circuit.

 

Ampere
A unit of measurement for electrical current or rate of flow of electrons (coulombs per second). If a group of electrons whose total charge is 1 coulomb passes a point in a conductor in 1 second, the electric current is 1 ampere. Its mathematical symbol is “I” the term is often shortened to “amps”.

 

ARC
Sparking that results when undesirable current flows between two points of differing potential. This may be due to leakage through the intermediate insulation or a leakage path due to contamination 

 

Attenuation
The reduction of a signal from one point to another. For an electrical surge, attenuation refers to the reduction of an incoming surge by a limiter (attenuator). Wire resistance, arresters, power conditioners attenuate surges to varying degrees.

 

AWG

This term refers to the U.S. standard for wire size.

 

Autotransformer

A transformer used to step voltage up or down. The primary and secondary windings share common turns, and it provides no isolation.

 

Auxiliary Source

A power source dedicated to providing emergency power to a critical load when commercial power is interrupted.

 

Balanced Load

An alternating current power system consisting of more than two current carrying conductors in which these conductors all carry the same current.

 

Battery

A collection of cells, grouped together to provide higher voltage and/or higher current than a single cell.

 

Battery Reservoir

A combination of cells or batteries used to power a UPS’s system inverter when it is in the emergency mode.

 

Battery Disconnect Switch

Master switch that disconnects a battery reservoir from a UPS. Provides personnel protection when batteries or UPS require service. 

 

Branch Circuit

A division of a load circuit with current limited by a fuse or circuit breaker.
 

Brownout

A low voltage condition lasting longer than a few cycles. “Brownouts” differ from “sags” only in duration.

 

BTU

British Thermal Unit. Energy required to raise one pound of water one degree Fahrenheit. One pound of water at 32 degrees F requires the transfer of 144 BTUs to freeze into solid ice.

 

Busbar

A heavy, rigid conductor used for high voltage feeders.

 

Capacitor
Two plates or conductors separated by an insulator. Applying a voltage across the plates causes current to flow and stores a charge. Capacitors resist changes in voltage.

Charger
An AC-to-DC converter which powers a UPS inverter and maintains the battery reservoir charge.

 

Conduit
A tubular raceway for data or power cables. Metallic conduit is common, although non-metallic forms may also be used. A conduit may also be a path or duct and need to be tubular.

Converter
A device which changes alternating current to direct current. 

Current
The movement of electrons through a conductor. Measured in amperes and its symbol is “I”.


Decibel
The standard unit for expressing relative power levels. Decibels indicate the ratio of power output to power input dB = 10 log10 (P1/P2).

Delta
A standard three phase connection with the ends of each phase winding connection in series to form a closed loop with each phase 120 electrical degrees from the other.

Delta-Delta
The connection between a delta source and a delta load.

Delta-Wye
The connection between a delta source and a wye load.
.

Direct Current
Electrical current which flows in one direction only.

Dropout
A discrete voltage loss. A voltage sag (complete or partial) for a very short period of time (milliseconds) constitutes a dropout.


Earth Ground
A low impedance path to earth for the purpose of discharging lightning, static, and radiated energy, and to maintain the main service entrance at earth potential.

 

Efficiency
The percentage of input power available for used by the load. The mathematical formula is: Efficiency = Po/ Pi Where “Po” equals power output, “Pi” equals power input, and power is represented by watts.

Electrical Degrees
One cycle of A.C. power is divided into 360 degrees. This allows mathematical relationships between the various aspects of electricity. 

 

EMI, RFI
Acronyms for various types of electrical interference: electomagnetic interference, radio frequency interference.

ESD
Electrostatic Discharge (static electricity). The effects of static discharge can range from simple skin irritation for an individual to degraded or destroyed semiconductor junctions for an electronic device. 

Farad
Unit of measurement for capacitance.

 

Filter
A selective network of resistor, inductors, or capacitors which offers comparatively little opposition to certain frequencies or direct current, while blocking or attenuating other frequencies. 

 

Flucuation
A surge or sag in voltage amplitude, often caused by load switching or fault clearing

 

Frequency
On AC circuits, designates number of times per second that the current completes a full cycle in positive and negative directions. See also “alternating current”.


GFI (Ground Fault Interrupter)
A device whose function is to interrupt the electric circuit to the load when a fault current to ground exceeds some predetermined value that is less than that required to operate the overcurrent protective device of the supply circuit.

Grounded
Connected to earth or to some conducting body that serves in place of the earth.

Ground Fault
Any undesirable current path from a current carrying conductor to ground.

Ground
Connection of one side of a circuit to the earth or a body that serves in place of the earth, through low impedance paths. Sometimes confused with bonding. Grounding should always conform to the National Electrical Code.

 

Harmonic
A sinusodial component of an AC voltage that is multiple of the fundamental waveform frequency.

Harmonic Distortion

Regularly appearing distortion of the sine wave whose frequency is a multiple of the fundamental frequency. Converts the normal sine wave into a complex waveform.


Hertz (HZ)
Unit of frequency, one hertz (Hz) equals one cycle per second.

Impedance
Forces which resist current flow in A.C. circuits, i.e. resistance, inductive reactance, capacitive reactance.

 

Inductance
The ability of a coil to store energy and oppose changes in current flowing through it. A function of the cross sectional area, number of turns of coil, length of coil and core material. 
.

Inverter
A device used to change DC into AC power.

Isolation Transformer
A multiple winding transformer with primary and secondary windings physically separated and designed to permit magnetic coupling between isolated circuits while minimizing electrostatic coupling. See also “electrostatic shield”.

Joule
s A watt/second. A measurement of work in time. 1 joule equals 0.0002778 watt/hours. 1 kilowatt hour is equivalent to 3,600,000 joules.

KVA
(Kilovolt amperes) (volts times amperes) divided by 1000. 1 KVA=1000 VA. KVA is actual measured power (apparent power) and is used for circuit sizing.

KW
(Kilowatts) watts divided by 1000. KW is real power and is important in sizing UPS, motor generators or other power conditioners. See also “power factor”.

KWH

(Kilowatt hours) KW times hours. A measurement of power and time used by utilities for billing purposes.

 
Lagging Load
An inductive load with current lagging voltage. Since inductors tend to resist changes in current, the current flow through an inductive circuit will lag behind the voltage. The number of electrical degrees between voltage and current is known as the “phase angle”. The cosine of this angle is equal to the power factor (linear loads only).

 

Leading Load
A capacitive load with current leading voltage. Since capacitors resist changes in voltage, the current flow in a capacitive circuit will lead the voltage.

Linear Load
A load in which the current relationship to voltage is constant based on a relatively constant load impedance.

Line Imbalance
Unequal loads on the phase lines of a multiphase feeder.

Load
The driven device that uses the power supplied from the source.

Load Balancing
Switching the various loads on a multi-phase feeder to equalize the current in each line.

Load Fault
A malfunction that causes the load to demand abnormally high amounts of current from the source.

 Main Service Entrance
The enclosure containing connection panels and switchgear, located at the point where the utility power lines enter a building.
 
Metal Oxide Varistor (MOV)
A MOV is a voltage sensitive breakdown device which is commonly used to limit overvoltage conditions (electrical surges) on power and data lines. When the applied voltage exceeds the breakdown point, the resistance of the MOV decreases from a very high level (thousands of ohms) to a very low level (a few ohms). The actual resistance of the device is a function of the rate of applied voltage and current

  

Negative Resistance
The characteristic of a circuit in which current varies inversely with applied voltage.

.

Neutral
The grounded junction point of the legs of a wye circuit. Or, the grounded center point of one coil of a delta transformer secondary. Measuring the phase to neutral voltage of each of the normal three phases will show whether the system is wye or delta. On a wye system, the phase to neutral voltages will be approximately equal and will measure phase to phase voltage divided by 1.73. On a center tapped delta system, one phase to neutral voltage will be significantly higher than the other two. This higher phase is often called the “high leg”.

Neutralizing Winding
An extra winding used to cancel harmonics developed in a saturated secondary winding, resulting in a sinusoidal output waveform from a ferroresonant transformer.

Nominal Voltage
The normal or designed voltage level. For three phase wye systems, nominal voltages are 480/277 (600/346 Canada) and 208/120 where the first number expresses phase to phase ( or line to line) voltages and the second number is the phase to neutral voltage. The nominal voltage for most single phase systems is 240/120.

Nonlinear Load
A load in which the current does not have a linear relationship to the voltage. In a light bulb, the current is directly proportional to voltage at all times. In a nonlinear load such as switched mode power supplies, the current is not directly proportional to voltage.

Normal Mode (NM)
The term refers to electrical interference which is measurable between line and neutral (current carrying conductors). Normal mode interference is readily generated by the operation of lights, switches and motors.

 OHM
The unit of measurement for electrical resistance or opposition to current flow.

OHM’S Law
The relationship between voltage (pressure), current (electron flow), and resistance. The current in an electrical circuit is directly proportional to the voltage and inversely proportional to the resistance. E=IR, or I=E/R, or R=E/I. Where E=voltage, I=current, and R=resistance.

 

Oscillation
The variation, usually with time, of the magnitude of quantity with respect to a specified reference when the magnitude is alternately greater and smaller than the reference.

.

Overvoltage
A voltage greater than the rating of a device or component. Normally overvoltage refers to long term events (several AC cycles and longer). The term can also apply to transients and surges.

 

Parallel Operation
The connection of the outputs of two or more power conditioners for use as one unit. Paralleling for capacity means that the units are paralleled for the sum of their individual ratings, i.e. two 125 KVA systems paralleled for use as a single 250 KVA system. Paralleling for redundancy means using one or more additional units to maintain power even when one unit fails..

Peak Line Current
Maximum instantaneous current during a cycle.

Phase Compensation
Switching capacitors into or out of a power distribution network to compensate for load power factor variations. 

Polyphase
An alternating current supply with two or more hot conductors. Voltage is measurable between the conductors and the voltage waveforms for each conductor are usually displaced 120 degrees. When a neutral is present, the voltage from each hot conductor to neutral is equal.

Power
Electrical energy measured according to voltage and current (normally watts). Power in watts equals volts times amperes for DC circuits. For single phase AC circuits, watts equal volts times amperes times power factor.

Power Factor
Watts divided by voltamps, KW divided by KVA. Power factor: leading and lagging of voltage versus current caused by inductive or capacitive loads, and 2) harmonic power factor: from nonlinear current.

Reactance
Opposition to the flow of alternating current. Capacitive reactance is the opposition offered by capacitor, and inductive reactance is the opposition offered by a coil or other inductance.

 

Rectifier
An electrical device used to change AC power into DC power. A battery charger is a rectifier.

Redundancy
The inclusion of additional assemblies and circuits (as within a UPS) with provision for automatic switchover from a failing assembly or circuit to its backup counterpart.

Reflection
The return wave generated when a traveling wave reaches a load, a source, or a junction where there is a change in line impedance.

Reliability
The statistical probability of trouble-free operation of a given component or assembly. Used principally as a function of MTBF and MTTR.

RFI
Radio Frequency Interference 

 
Safety Ground
An alternate path of return current, during a fault condition, for the purpose of tripping a circuit breaker. Also, the means of establishing a load at earth level.

SAG
A short duration low voltage condition.
 
Semiconductor
A semiconductor is an electronic conductor (ex., silicon, selenium or germanium) with a resistivity between metals and insulators. Current flows through the semiconductor normally via holes or electrons.

Service Factor
(Of a motor) a measurement of the motor’s ability to operate under abnormal conditions. A 1.15 times its rated load continuously when operated at its rated voltage, frequency, temperature, etc. Therefore, a 125 horsepower motor could be operated as a 143.75 h.p. motor under normal conditions.

Shielding
Imposing a metallic barrier to reduce the coupling of undesirable signals.

 

Single Phase
(With a three phase source) one or tow phase conductors. (Single phase source) A single output which may be center tapped for dual voltage levels.

  

Soft-Start Circuit
Circuitry that limits the initial power demand when a UPS has been operating in emergency mode and commercial power is restored. Also, it controls the rate at which UPS output increases to normal.

Steady State
A condition in which circuit values remain essentially constant after all initial fluctuating conditions have settled down.

 

Substation
Location where high voltage transmission lines connect to switchgear and step-down transformers to produce lower voltages at lower power levels for local distribution networks.

Surge
A short duration high voltage condition. A surge lasts for several cycles where a transient lasts less than one half cycle. Often confused with “transient”.

Switch Gear
A group of switches, relays, circuit breakers, etc. Used to control distribution of power to other distribution equipment and large loads.

Synchronization
Maintaining a constant phase relationship between AC signals.

 
Synchronous Motor
An AC motor whose speed is exactly proportional to the power input frequency.


TAP
A connection point brought out of a transformer winding to permit changing the turns ratio.

 

 Three Phase Power

Three separate outputs from a single source with a phase differential of 120 electrical degrees between any two adjacent voltages or currents. Mathematical calculations with three-phase power must allow for the additional power delivered by the third phase. Remember, both single phase and three phase have the same phase to phase voltages, therefore you must utilize the square root of 3 in your calculations. For example, KVA equals volts times amps for DC and for single phase. For three phase the formula is volts times the square root of three times amps.
 

Total Harmonic Distortion (THD)

The square root of the sum of the squares of the RMS harmonic voltages or currents divided by the RMS fundamental voltage or current. Can also be calculated in the same way for only even harmonics or odd harmonics.

Transducer
A device that senses one form of energy and converts it to another, i.e., temperature to voltage (for monitoring).

Transfer Switch
A switch used to transfer a load between a UPS and its bypass source.

Transformer
A static electrical device which, by electromagnetic induction, regenerates A.C. power from one circuit into another. Transformers are also used to change voltage from one level to another. This is accomplished by the ratio of turns on the primary to turns on the secondary (turns ratio). If the primary windings have twice the number of windings as the secondary, the secondary voltage will be half of the primary voltage.

 

Transient Response

The ability of a power conditioner to respond to a change. Transient step load response is the ability of a power conditioner to maintain a constant output voltage when sudden load (current) changes are made.

UPS
Uninterruptible Power Source.

VAC
Volts of alternating current.

VDC
Volts of direct current.

Volt (V)
The unit of voltage or potential difference. 

Voltage
Electrical pressure, the force which causes current to flow through a conductor. Voltage must be expressed as a difference of potential between two points since it is a relational term. Connecting both voltmeter leads to the same point will show no voltage present although the voltage between that point and ground may be hundred or thousands of volts. This is why most nominal voltages are expressed as “phase to phase” or “phase to neutral”. The unit of measurement is “volts”. The electrical symbol is “e”.

 

Watt (W)

The unit of power. Equal to one joule per second.

 

WYE

A wye connection refers to a polyphase electrical supply where the source transformer has the conductors connected to the terminals in a physical arrangement resembling a Y. Each point of the Y represents the connection of a hot conductor. The angular displacement between each point of the Y is 120 degrees. The center point is the common return point for the neutral conductor.